Reading Configuration Menu
14
2.Cd In
READING SCALE & OFFSET 2-COORDINATE FORMAT MENU:
Input voltage or current can be converted or scaled into values appropriate for the process or signal
being measured. A reading may be displayed, for example, in units of weight or velocity instead of in
amperes and volts.
The controller determines scale and offset values based on two user-provided input
values entered with the corresponding readings.
There are two methods to scale this meter to display readings in engineering units.
• The first method "ON.L INE" is to scale with known loads. Do this by applying known loads to a
transducer connected to a meter, or by simulating the output of the transducer with voltage or
current simulator.
• The second method "MANUAL" is to scale without known inputs. Do this by calculating input
values based on transducer specifications and manually entering them through the keyboard.
Press ‘RESET/ENTER’ 17) Display shows "2.Cd INt" (2-coordinate format) and stops flashing if
display was prompted "2.Cd INt".
If this scaling method is selected, calculate the input values to the
instrument based on the actual signal being received.
ON.L INE
Press ‘RESET/ENTER’ 18) Display flashes "ON.L INE" On line method.
Press ‘䊱/MAX’ 19) Scroll between 2 available selections: "ON.L INE” or "MANUAL" for
the configuration option of your choice. If your choice of selection is
"MANUAL", skip to Step 28).
Press ‘RESET/ENTER’ 20) Display stops flashing and shows "ON.L INE".
Press ‘RESET/ENTER’ 21)
Display shows "INPUt 1" Item #1 of coordinate #1.
Pressing
‘RESET/ENTER’ to sequence through:
"INPUt 1", Input 1 ’s value
"REAd 1", Read 1 ’s value
"INPUt 2", Input 2 ’s value
"REAd 2", Read 2 ’s value
headings for the desired selection to enter new value.