OMICRON 177
Error and warning messages
204.xxx Warning [204.xxx] Check CT SB2 switch box wiring: Wrong polarity at PRIM terminal.
Reason: Input signal at input "PRIM" differs from the expected one: Reverse polarity at CT SB2
input "PRIM".
Solution: Check whether the PRIM IN sockets on the CT SB2 are connected properly and with
correct polarity. If necessary, connect with changed polarity.
205.xxx Warning [205.xxx] Check connection. Input PRIM may be disconnected.
Reason: Input signal at input "Prim" differs from the expected one.
Solution: Check whether the output generator ("Output") and measurement input "Prim" are
connected properly.
205.xxx Warning [205.xxx] Check CT SB2 switch box wiring: PRIM IN terminal may be disconnected.
Reason: Input signal at input "Prim" differs from the expected one.
Solution: Check whether the PRIM IN sockets on the CT SB2 are connected properly.
206.xxx Warning [206.xxx] Check connection. Ensure that the output is connected to the primary side of
the CT.
Reason: Input signal at input "Prim" differs from the expected one.
Solution: Check that the output generator ("Output") is connected to the CT and that the primary side
of the CT is connected to input "Prim".
206.xxx Warning [206.xxx] Check CT SB2 switch box wiring: CTA OUTPUT and/or PRIM OUT terminal may
be disconnected.
Reason: Input signal at input "Prim" differs from the expected one.
Solution: Check whether the PRIM OUT and the PRIM IN sockets on the CT SB2 are connected
correctly to the primary side of the CT.
207.xxx Warning [207.xxx] Check connection! OUTPUT may be disconnected.
Reason: The current signal differs from the expected one.
Solution: Check whether the output generator ("Output") and measurement input "SEC" are
connected properly to the secondary side of the CT.
210.xxx Warning [210.xxx] Permanent data overflow.
Reason: Internal data buffer overflow. The data could not be fetched fast enough from the internal
data buffer.
Solution: Try to repeat the measurement. If this error occurs more frequently, you should contact
your next OMICRON service center.
211.xxx Warning [211.xxx] Sinus mode measurement timeout.
Reason: Measurement timeout due to frequent range switching or invalid data from the
measurement inputs.
Solution: Check the wiring and repeat the measurement. Try to reduce noise for the measurement.
220.xxx Warning [220.xxx] Test aborted!
Reason: The test sequence has been interrupted by the user.
Solution: Repeat the test without interrupting it.
308.xxx Note [308.xxx] I-sn value has to be specified in CT-Object Card prior to Residual Magnetism test!
Reason: For the remanence test the I
sn
value should be defined.
Solution: Enter valid I
sn
value before starting the remanence test.
310.xxx Note [310.xxx] License: <Guesser functionality> is missing! Values for: Ipn, Isn, P/M, Class,
FS/ALF should be provided.
Reason: The license required for class guessing is not available.
Solution: Specify the values for I
pn
, I
sn
, Class, P/M and FS/ALF before starting the test.
311.xxx Warning [311.xxx] License: <Simulation after test> is missing!
Reason: The license required for simulation is not available.
Solution: Simulation of the results for changed test settings (e.g. different burden values) after the
test is not possible. Purchase a corresponding license.
312.xxx Warning [312.xxx] License: <...> is missing!
Reason: The license specified in the message is not available.
Solution: The functionality included in the license is not available. Purchase a corresponding license.