CT Analyzer User Manual
44 OMICRON
3.6 Disconnection
Proceed as follows to disconnect CT Analyzer:
1. Wait until the red LED on CT Analyzer is off.
2. Disconnect the measurement leads starting at CT Analyzer.
WARNING
Death or severe injury caused by high voltage or current possible
As long as the red LED on CT Analyzer is flashing, the output is active and lethal
voltages can occur due to the high energy stored in external inductors.
Do not disconnect measurement leads while the red LED on CT Analyzer is flashing.
Always wait until the red LED is off before disconnecting measurement leads.