EasyManua.ls Logo

Omron CP1L - Page 225

Omron CP1L
763 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
191
High-speed Counters Section 5-1
I/O Allocations
Input Terminals
Note The high-speed counter inputs are enabled when the
Use high speed counter
0
Option is selected in the PLC Setup’s Built-in Input Tab.
Output Terminals
Auxiliary Area Addresses for High-speed Counter 0
Range Comparison Table
The range comparison table is stored in D10000 to D10039.
PLC Setup
Select the
Use high speed counter 0
Option in the PLC Setup’s Built-in Input
Tab.
Input terminal Usage
Word Bit
CIO 0 00 High-speed counter 0 phase-A input (See note.)
01 High-speed counter 0 phase-B input (See note.)
02 Start measurement by pushbutton switch (normal input).
03 Detect trailing edge of measured object (normal input).
04 Detect leading edge of measured object for high-speed counter 0
phase-Z/reset input (see note). Bit status is reflected in A531.00.
05 to 11 Not used. (normal input)
CIO 1 00 to 11 Not used. (normal input)
Output terminal Usage
Word Bit
CIO 100 00 Normal input PL1: Dimension pass output
01 Normal input PL2: Dimension fail output
02 to 07 Normal input Not used.
CIO 101 00 to 07 Normal input Not used.
Function Address
PV storage words Leftmost 4 digits A271
Rightmost 4 digits A270
Range Comparison
Condition Met Flag
Range 1 Comparison Condition Met Flag A274.00
Comparison In-
progress Flag
ON when a comparison operation is being exe-
cuted for the high-speed counter.
A274.08
Overflow/Underflow
Flag
ON when an overflow or underflow has occurred
in the high-speed counter’s PV. (Used only when
the counting mode is set to Linear Mode.)
A274.09
Count Direction Flag 0: Decrementing
1: Incrementing
A274.10
Reset Bit Used for the PV software reset. A531.00
High-speed Counter
Gate Bit
When ON, the counter's PV will not be changed
even if pulse inputs are received for the counter.
A531.08
Item Setting
High-speed counter 0 Use high speed counter 0
Counting mode Linear mode
Circular Max. Count ---
Reset method Software reset
Input Setting Up/Down inputs

Table of Contents

Other manuals for Omron CP1L

Related product manuals