203
Pulse Outputs Section 5-2
■ Setting Functions Using Instructions and PLC Setup
■ Input Terminal Block Arrangements
CPU Unit with 10 I/O Points
CPU Unit with 14 I/O Points
Input 
terminal 
block
When the 
instructions to 
the right are not 
executed
When a pulse output instruction 
(SPED, ACC, PLS2, or ORG) is executed
When the origin search 
function is enabled in 
the PLC Setup, and an 
origin search is 
executed by the ORG 
instruction
When the PWM 
instruction is 
executed
Word Bit Normal output Fixed duty factor pulse output Variable duty 
factor pulse output
CW/CCW Pulse plus direction When the origin search 
function is used
PWM output
CIO 
100
00 Normal output 0 Pulse output 0 (CW) 
fixed
Pulse output 0 (pulse) 
fixed
--- ---
01 Normal output 1 Pulse output 0 (CCW) 
fixed
Pulse output 0 (direction) 
fixed
--- PWM output 0
02 Normal output 2 Pulse output 1 (CW) 
fixed
Pulse output 1 (pulse) 
fixed
--- ---
03 Normal output 3 Pulse output 1 (CCW) 
fixed
Pulse output 1 (direction) 
fixed
--- PWM output 1
04 Normal output 4 --- --- Origin search 0 (Error 
counter reset output)
---
05 Normal output 5 --- --- Origin search 1 (Error 
counter reset output)
---
06 Normal output 6 --- --- --- ---
07 Normal output 7 --- --- --- ---
CIO 
101
00 to 
07
Normal output 8 
to 15
--- --- ---
Upper Terminal Block
(Example: DC Power 
Supply Modules)
Pulse 0: Origin proximity input signal
Pulse output 0: Origin input signal
+-
COM 01 03 05
NC
 
00 02 04
Upper Terminal Block  
(Example: DC Power  
Supply Models)
Pulse 0: Origin proximity input signal
Pulse 1: Origin proximity input signal
 
Pulse output 1: Origin input signal
Pulse output 0: Origin input signal
COM
01 03 05 07
00 02 04 06
NC
+ −
NC NC
NC NC