344
Interrupt Functions Section 6-1
Setting the Input Functions in the PLC Setup
Normally, bits CIO 0.04 to CIO 0.09 are used as normal inputs. When using
these inputs for input interrupts, use the CX-Programmer to change the
input’s setting in the PLC Setup.
Note *Input interrupts 4 and 5 are not supported by CPU Units with 10 or 14 I/O
Points.
**Input interrupts 2 and 3 are not supported by CPU Units with 10 I/O Points.
Procedure
Input terminal
block
CPU Unit Input
interrupt
Task
number
Word Bit
CPU Units with
60 I/O Points
CPU Units with
40 I/O Points
CPU Units with
30 I/O Points
CPU Units with
20 I/O Points
CPU Units with
14 I/O Points
CPU Units with
10 I/O Points
CIO 0 00 Normal input 0 Normal input 0 Normal input 0 Normal input 0 Normal input 0 Normal input 0 --- ---
01 Normal input 1 Normal input 1 Normal input 1 Normal input 1 Normal input 1 Normal input 1 --- ---
02 Normal input 2 Normal input 2 Normal input 2 Normal input 2 Normal input 2 Normal input 2 --- ---
03 Normal input 3 Normal input 3 Normal input 3 Normal input 3 Normal input 3 Normal input 3 --- ---
04 Normal input 4 Normal input 4 Normal input 4 Normal input 4 Normal input 4 Normal input 4 Input
interrupt 0
Interrupt
task 140
05 Normal input 5 Normal input 5 Normal input 5 Normal input 5 Normal input 5 Normal input 5 Input
interrupt 1
Interrupt
task 141
06 Normal input 6 Normal input 6 Normal input 6 Normal input 6 Normal input 6 --- Input
interrupt
2**
Interrupt
task
142**
07 Normal input 7 Normal input 7 Normal input 7 Normal input 7 Normal input 7 --- Input
interrupt
3**
Interrupt
task
143**
08 Normal input 8 Normal input 8 Normal input 8 Normal input 8 --- --- Input
interrupt
4*
Interrupt
task
144*
09 Normal input 9 Normal input 9 Normal input 9 Normal input 9 --- --- Input
interrupt
5*
Interrupt
task
145*
10 Normal input
10
Normal input
10
Normal input
10
Normal input
10
--- --- --- ---
11 Normal input
11
Normal input
11
Normal input
11
Normal input
11
--- --- --- ---
CIO 1 00 to
05
Normal input
12 to 17
Normal input
12 to 17
Normal input
12 to 17
--- --- --- --- ---
06 to
11
Normal inputs
18 to 23
Normal inputs
18 to 23
--- --- --- --- --- ---
CIO 2 00 to
11
Normal inputs
24 to 35
--- --- --- --- --- --- ---
Select the input interrupts.
• Determine the inputs to be used for input
interrupts and corresponding task numbers.
↓
Wire the inputs. • Wire the inputs.
↓
Set the PLC Setup.
• Use the CX-Programmer to select the inter-
rupt inputs in the PLC Setup.
↓
Write the ladder program.
• Write the programs for the corresponding
interrupt task numbers.
• Use MSKS(690) to specify up-differentiation
or down-differentiation.
• Use MSKS(690) to enable input interrupts (in
direct mode).