EasyManua.ls Logo

Omron CP1L - Page 378

Omron CP1L
763 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
344
Interrupt Functions Section 6-1
Setting the Input Functions in the PLC Setup
Normally, bits CIO 0.04 to CIO 0.09 are used as normal inputs. When using
these inputs for input interrupts, use the CX-Programmer to change the
input’s setting in the PLC Setup.
Note *Input interrupts 4 and 5 are not supported by CPU Units with 10 or 14 I/O
Points.
**Input interrupts 2 and 3 are not supported by CPU Units with 10 I/O Points.
Procedure
Input terminal
block
CPU Unit Input
interrupt
Task
number
Word Bit
CPU Units with
60 I/O Points
CPU Units with
40 I/O Points
CPU Units with
30 I/O Points
CPU Units with
20 I/O Points
CPU Units with
14 I/O Points
CPU Units with
10 I/O Points
CIO 0 00 Normal input 0 Normal input 0 Normal input 0 Normal input 0 Normal input 0 Normal input 0 --- ---
01 Normal input 1 Normal input 1 Normal input 1 Normal input 1 Normal input 1 Normal input 1 --- ---
02 Normal input 2 Normal input 2 Normal input 2 Normal input 2 Normal input 2 Normal input 2 --- ---
03 Normal input 3 Normal input 3 Normal input 3 Normal input 3 Normal input 3 Normal input 3 --- ---
04 Normal input 4 Normal input 4 Normal input 4 Normal input 4 Normal input 4 Normal input 4 Input
interrupt 0
Interrupt
task 140
05 Normal input 5 Normal input 5 Normal input 5 Normal input 5 Normal input 5 Normal input 5 Input
interrupt 1
Interrupt
task 141
06 Normal input 6 Normal input 6 Normal input 6 Normal input 6 Normal input 6 --- Input
interrupt
2**
Interrupt
task
142**
07 Normal input 7 Normal input 7 Normal input 7 Normal input 7 Normal input 7 --- Input
interrupt
3**
Interrupt
task
143**
08 Normal input 8 Normal input 8 Normal input 8 Normal input 8 --- --- Input
interrupt
4*
Interrupt
task
144*
09 Normal input 9 Normal input 9 Normal input 9 Normal input 9 --- --- Input
interrupt
5*
Interrupt
task
145*
10 Normal input
10
Normal input
10
Normal input
10
Normal input
10
--- --- --- ---
11 Normal input
11
Normal input
11
Normal input
11
Normal input
11
--- --- --- ---
CIO 1 00 to
05
Normal input
12 to 17
Normal input
12 to 17
Normal input
12 to 17
--- --- --- --- ---
06 to
11
Normal inputs
18 to 23
Normal inputs
18 to 23
--- --- --- --- --- ---
CIO 2 00 to
11
Normal inputs
24 to 35
--- --- --- --- --- --- ---
Select the input interrupts.
Determine the inputs to be used for input
interrupts and corresponding task numbers.
Wire the inputs. Wire the inputs.
Set the PLC Setup.
Use the CX-Programmer to select the inter-
rupt inputs in the PLC Setup.
Write the ladder program.
Write the programs for the corresponding
interrupt task numbers.
Use MSKS(690) to specify up-differentiation
or down-differentiation.
Use MSKS(690) to enable input interrupts (in
direct mode).

Table of Contents

Other manuals for Omron CP1L

Related product manuals