623
Auxiliary Area Allocations by Address Appendix D
A36 00 Operation
Command
Flag 1
This flag turns ON during an opera-
tion command for inverter positioning
1.
ON: Opera-
tion command
executed.
OFF: Stop
command
executed.
--- Cleared When
inverter
positioning
1 is started
---
01 Forward Oper-
ation Com-
mand Flag 1
This flag turns ON during a forward
operation command for inverter posi-
tioning 1.
ON: Forward
command in
progress
OFF: Reverse
command in
progress or
stopped
--- Cleared When
present
value of
error
counter 1
is positive
---
02 Reverse Oper-
ation Com-
mand Flag 1
This flag turns ON during a reverse
operation command for inverter posi-
tioning 1.
ON: Reverse
command in
progress
OFF: For-
ward com-
mand in
progress or
stopped
--- Cleared When
present
value of
error
counter 1
is negative
---
03 In-position
Flag 1
This flag turns ON when inverter
positioning 1 is in position.
ON: In posi-
tion
OFF: Not in
position
--- Cleared When
pulse out-
put to error
counter 1
is stopped
and the
present
value of
error
counter 1
is within
the in-posi-
tion range
---
04 Error Counter
Error Flag 1
This flag turns ON when an error
occurs in the error counter for
inverter positioning 1.
ON: Error
counter error
OFF: No error
--- Cleared When
pulse out-
put to error
counter is
stopped
and abso-
lute value
of error
counter
present
value is
greater
than or
equal to
error
counter
error
detection
value
---
05 Error Counter
Pulse Output
Flag 1
This flag is ON while pulses are
being output to the output counter for
inverter positioning 1.
ON: Pulses
being output
OFF: Pulse
output
stopped
--- Cleared When
pulse out-
put to error
counter 1
is started
---
06 Error Counter
Pulse Output
Acceleration/
Deceleration
Flag 1
This flag is ON while pulse output to
the output counter for inverter posi-
tioning 1 is accelerating or decelerat-
ing.
ON: Pulse
output to the
error counter
is accelerat-
ing or decel-
erating (i.e.,
the fre-
quency is
changing)
OFF: Pulse
output to the
error counter
is constant
--- Cleared When
pulse out-
put fre-
quency to
error
counter is
changed
by ACC or
PLS2
instruction
---
Address Name Function Settings Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words Bits