336
Binary Calculation Instructions Section 5-22
Description MBSL(––) multiplies the 32-bit (8-digit) signed binary data in Md+1 and Md
with the 32-bit signed binary data in Mr+1 and Mr, and outputs the 16-digit
signed binary result to R+3 through R.
Note Refer to 1-7 Calculating with Signed Binary Data for more details.
Flags ER: Indirectly addressed EM/DM word is non-existent.
(Content of *EM/*DM word is not BCD, or the EM/DM area boundary
has been exceeded.)
EQ: ON when the result is zero (content of R+3 through R all zeroes), oth-
erwise OFF.
Example In the following example, MBSL(––) is used to multiply the signed binary con-
tents of IR 101 and IR 100 with the signed binary contents of DM 0021 and
DM 0020 and output the result to LR 24 through LR 01.
5-22-9 SIGNED BINARY DIVIDE – DBS(––)
Limitations DM 6143 to DM 6655 cannot be used for R.
Md + 1 Md
Mr + 1 Mr
R + 1 RR + 3 R + 2
x
MBSL(−−)
100
DM 0020
LR 01
Address Instruction Operands
00000 LD 00000
00001 MBSL(−− )
100
DM 0020
LR 21
00000
Md: IR 100
7 9 3 8
Mr: DM 0020
A 8 1 2
R: LR 01
4 5 F 0
R+1: LR 02
F C A 5
(555,320)
(1,005,550)
(55,840,206,000)
Md+1: IR 101
0 0 0 8
Mr+1: DM 0021
F F F 0
X
R+2: LR 03
F F 7 D
R+3: LR 04
F F F F
Dd: Dividend word
IR, SR, AR, DM, EM, HR, TIM/CNT, LR, #
Dr: Divisor word
IR, SR, AR, DM, EM, HR, TIM/CNT, LR, #
Ladder Symbols
Operand Data Areas
R: First result word
IR, SR, AR, DM, EM, HR, LR
DBS(−− )
Dd
Dr
R
@DBS(−− )
Dd
Dr
R