PART 2: CX-Server PLC Tools
CHAPTER 10 – Data Links OMRON
CX-Server PLC Tools_Page 104
Item Data set Description
Ordered destination nodes 1, 2, 3 Specifies the node refresh sequence.
Beginning with the start addresses, nodes
01, 02, and 03 are set in order. (The local
node address is 1, so transmission is first,
followed by reception from node 02, and
finally reception from node 03.)
Memory area CIO Status
Start address 1100
Sets CIO 1100 as the data link status start
address.
8 Set node address 02 as shown in the following table.
Item Data set Description
Node address 2
−
PLC type CS1G-CPU45
−
Memory area CIO
Start address 1200
Sets CIO 1200 as the data link start
address for the Area 1 local node.
Area 1
Send size 30 Sets 30 words as the send size (unit:
words) for the Area 1 local node.
Memory area D
Start address 600
Sets D00600 as the data link start address
for the Area 2 local node.
Area 2
Send size 30 Sets 30 words as the send size (unit:
words) for the Area 2 local node.
Ordered destination nodes 1, 2, 3 Specifies the node refresh sequence.
Beginning with the start addresses, nodes
01, 02, and 03 are set in order. (Reception
from node 01 is first, followed by
transmission from the local node, and
finally reception from node 03.)
Memory area CIO Data link status
start address
Start address 1300
Sets CIO 1300 as the data link status start
address.
9 Set node address 03 as shown in the following table, and then click the Next button or press the Enter key.
Item Data set Description
Node address 3
−
PLC type C200HX
−
Memory area IR
Start address 300
Sets IR 300 as the data link start address
for the Area 1 local node.
Area 1
Send size 40 Sets 40 words as the send size (unit:
words) for the Area 1 local node.
Memory area DM
Start address 700
Sets DM 700 as the data link start address
for the Area 2 local node.
Area 2
Send size 40 Sets 40 words as the send size (unit:
words) for the Area 2 local node.
Ordered destination nodes 2, 1, 3 Specifies the node refresh sequence.
Beginning with the start addresses, nodes
02, 01, and 03 are set in order. (Reception
from node 02 is first, followed by reception
from node 01, and finally transmission from
the local node address.)
Memory area LR Data link status
start address
Start address 0
Sets LR0 as the data link status start
address.