PART 2: CX-Server PLC Tools
OMRON CHAPTER 10 – Data Links
CX-Server PLC Tools_ Page 103
No. Item Function
(4) Start Address Area 1 start address
Area 2 start address
(5) Size Area 1 local node send size (in words)
Area 2 local node send size (in words)
(6) Status Data link status memory area (See note.)
(7) Ordered Destination
Nodes
Node Refresh Sequence
Beginning with the data link start address above, specify which nodes are to
have data refreshed at the local node address and the order in which data is to
be refreshed (i.e., the node refresh sequence). This order will be the same for
Area 1 and Area 2.
(For the local node address, data is sent from the local node area. For a
remote node address, data is received from the remote node address to the
local area.)
Note:
• The local node must be included in the refresh nodes.
• If the address of any node participating in the data links is not entered
here, data will not be received from that node.
Example: If 1, 2, 3 is input, node addresses 1, 2, and 3 will be allocated in
order, beginning with the start address.
(8) Make Default Click this button to make the values set for the above items the default values
for new data link settings.
(9) Next >> Click to proceed to the next dialog box.
Note: The default setting for data link status depends on the PLC being used. For details, refer to the
Controller Link Units Operation Manual (W309).
PLC Data link status
CS/CJ Series
CVM1/CV Series
The data link status is contained in the 16 words (fixed) from CIO 1500 +25
× unit number + 7
to 22 in the CPU Bus Unit Area.
15 8 7 0
+7 words Node 2 Node 1
... ... ...
+22 words Node 32 Node 31
C200HX/HG/HE The data link status for node addresses 1 to 6 only is contained in the words from SR 239 to
SR 241, and SR 241 to SR 245.
Network 0 Network 1 15 8 7 0
SR 239 SR 243 Node 2 Node 1
SR 240 SR 244 Node 4 Node 3
SR 241 SR 245 Node 6 Node 5
CQM1H Series The data link status for node addresses 1 to 6 only is contained in the words from IR 91 to IR
93.
15 8 7 0
IR 91 Node 2 Node 1
IR 92 Node 4 Node 3
IR 93 Node 6 Node 5
7 Set node address 01 as shown in the following table, and then click the Next button or press the Enter key. Set
node addresses 02 and 03 in the same way.
Item Data set Description
Node address 1
−
PLC type CS1G-CPU45
−
Memory area CIO
Start address 1000
Sets CIO 1000 as the data link start
address for the Area 1 local node.
Area 1
Send size 30 Sets 30 words as the send size (unit:
words) for the Area 1 local node.
Memory area D
Start address 500
Sets D00500 as the data link start
address for the Area 2 local node.
Area 2
Send size 30 Sets 30 words as the send size (unit:
words) for the Area 2 local node.