4 Parameter List
4 - 27
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Changes
during
RUN
Unit
Page
Level and output
terminal
status
C038
Low Current Signal
Output Selection
00: Enabled during acceleration/decel-
eration and constant speed
01: Enabled during constant speed
01
Enabled
P. 7-89
C039
Low Current Detec-
tion Level
0.00 Rated current to 2.00 Rated cur-
rent
Rated
current
Enabled
A
C040
Overload Warning
Signal Output Selec-
tion
00: Enabled during acceleration/decel-
eration and constant speed
01: Enabled during constant speed
01
Enabled
P. 7-80
C041
1st Overload Warn-
ing Level
0.00: Overload warning disabled
0.01 Rated current to 2.00 Rated cur-
rent
Rated
current
1.15
Enabled
A
C241
2nd Overload Warn-
ing Level
Rated
current
1.15
Enabled
4
4-3 Extended Function Mode
4-3-3 Group C: Multi-function Terminal Function Parameters