EasyManua.ls Logo

Omron TJ1-MC04 - PROGRAMMING 1 - Inverter_Write

Omron TJ1-MC04 - PROGRAMMING 1
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BASIC commands
PROGRAMMING MANUAL 102
Revision 3.0
/i
3.2.160 INVERTER_WRITE
/i
Arguments module
The number of the TJ1-ML__ that the inverter is connected to.
station
The MECHATROLINK-II station number of the inverter.
param_number
The number of the parameter to read. See the inverter manual.
param_size
The size of the parameter to read, 2 or 4 bytes. See the inverter manual.
VR
The address in the VR memory of the TJ-MC__ where the read informa-
tion is put. When the function is 4, the result is returned as a bitwise
value. See the table below.
alarm_number
The number of the alarm to read. See the inverter manual.
from
The start address of the input to read.
length
The length of the input to read.
Example No example.
See also N/A
Bit Value Command Description
0 Hex 1 Run forward
1 Hex 2 Run reverse
2 Hex 4 Inverter multifunction Input 3
3 Hex 8 Inverter multifunction Input 4
4 Hex 10 Inverter multifunction Input 5
5 Hex 20 Inverter multifunction Input 6
6 Hex 40 Inverter multifunction Input 7
8 Hex 100 External fault
9 Hex 200 Fault reset
14 Hex 4000 Fault history data clear
15 Hex 8000 External BB command
Type System command
Syntax INVERTER_WRITE(module, station, 0, param_number, param_size, VR,
mode)
INVERTER_WRITE(module, station, 2, value)
INVERTER_WRITE(module, station, 3, value)
Description INVERTER_WRITE writes the parameter, speed reference or torque refer-
ence from the frequency inverter connected to the system via the MECHA-
TROLINK-II bus.
There are three INVERTER_WRITE functions:
0: Writes an inverter parameter.
2: Writes the speed reference.
3: Writes the torque reference.
To use an inverter via MECHATROLINK-II you should put the command and
the reference via communication option:
Inverter MV/V7: N3=3; N4=9
Inverter F7/G7: B1-01=3; B1-02=3.
Make you sure that the Inverter firmware supports the MECHATROLINK-II
board.
The command returns -1 if successfully executed and 0 if failed. The result (if
any) is returned in the selected VR.
I52E-EN-03.book Seite 102 Freitag, 29. Juni 2007 11:55 11

Table of Contents

Related product manuals