Function description
Operating Manual PNOZ s30
1001715-EN-19
| 36
} Error acknowledgement
When switching to the parameter set, the recoverable errors are acknowledged. Errors
that occur while the parameter set is executed are not acknowledged. After error acknow-
ledgement the device behaves in accordance with the switching functions configured in
this parameter set. A new error acknowledgement by this parameter set can only be per-
formed after selecting another parameter set.
A complete list of recoverable errors can be found under Current error
messages [ 92].
The error acknowledgement restarts the PNOZ s30.
} Restart
The device is restarted when switching to the parameter set.
After restart the device behaves in accordance with the switching functions configured in
this parameter set. A new restart by this parameter set can only be performed after se-
lecting another parameter set.