Function description
Operating Manual PNOZ s30
1001715-EN-19
| 33
5.4.2 Switch functions
The following switch functions are available:
} Standstill
The standstill frequency is configured centrally. The standstill frequency should be the
lowest frequency in the configuration.
All switch function parameters are pre-configured to the lowest frequency in the factory
setting.
} Speed
Limit values can be configured to monitor for overspeed.
Limit values should be entered in ascending order (Parameter set P0 → lowest values,
parameter set P15 → highest values)
} Speed range
Up to 4speed ranges can be monitored simultaneously.
Configure two switch functions (speeds) to monitor a range:
– F2 and F3,
– F4 and F5,
– F6 and F7 or
– F8 and F9.
The switch function with the lower number (e.g. F2) operates as the lower range limit; the
switch function with the higher number (e.g. F3) operates as the upper range limit.
Both switch functions can be assigned to one or more outputs.
} Position
Up to 4 different position windows can be monitored: Position 1 ... Position 4.
Each position to be monitored can be entered as often as necessary in parameter sets
P0 to P15 and switch functions F1 to F9.
} Direction
The monitoring functions "Direct. Left" and "Direct. Right" can be configured as a switch
function as often as necessary.
For both directions, a tolerance can be entered for the wrong direction.
} Static value "On" or "Off"
The static value "On" or "Off" can be configured as a switch function instead of a monitor-
ing function. The assigned outputs are then switched on and/or off.
The static value "On" and "Off" can be configured as a switch function as often as neces-
sary.