EasyManuals Logo

Pilz PNOZ s30 User Manual

Pilz PNOZ s30
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #66 background imageLoading...
Page #66 background image
Display menu - Configuration
Operating Manual PNOZ s30
1001715-EN-19
| 66
7. When Data read successfully is displayed on the software interface, the data can be
saved as a hex file in any directory on the computer.
8. Make sure that the corresponding configuration CRC, which you noted down, is saved
in the same directory.
Download configuration from the computer to the PNOZ s30
1. Insert a chip card into the holder for the chip card reader and insert this into the chip
card reader.
2. Start the SmartCardCommander software.
3. To write the chip card, select Write Data to Card and confirm with Yes.
4. Insert the chip card in the PNOZ s30 and proceed as described under Read data from
chip card [ 61].
5. To ensure that the configuration has been transferred correctly, check that the CRC for
the configuration in the PNOZ s30 matches the configuration CRC you noted down on
the computer.
CAUTION!
With each transfer, you must check that the appropriate configuration for an
application is transferred to a device!