Display menu - Configuration
Operating Manual PNOZ s30
1001715-EN-19
| 69
Level Designation
on the display
Description Settings
2 Standstill
Rel.1 Out 1
Default:
100 Hz
Enter standstill frequency 10 mHz to 1.00 kHz
2 v max
Rel.2 Out 2
Default:
5.00 kHz
Enter the max. permitted speed 10 mHz to 1.00 MHz
Other, pre-defined settings:
} Switch functions
– Direction (F3)
Left direction
Tolerance for wrong direction = 10 pulses
– Direction (F4)
Right direction
Tolerance for wrong direction = 10 pulses
} Parameter set/select input
P0, select inputs are ignored (Select inputs mode: "None ")
} Hysteresis
Standstill and speed, 2 % each
} Output assignment
– Standstill: Relay output Rel. 1 and semiconductor output Out 1
– Speed: Relay output Rel. 2 and semiconductor output Out 2
– Left direction: External output Ext. 1 and semiconductor output Out 3
– Right direction: External output Ext. 2 and semiconductor output Out 4
} Start mode
– All outputs: Automatic start ("Automatic")
} Switch delay
None
} Max. encoder frequency
1 MHz