4 | Description of project
Page 18 of 104 CIRUS
®
UPT-6400 VERSION 1 | EN-US
Install unfiltered and filtered lines in separate wiring ducts.
Follow the instructions in the line filter operating instructions.
Comply with the application report.
4.5.6 Measurement cable
Use a twisted measurement cable supplied by ROPEX (UML-1 or UML-2). Connect
the measurement cable directly to the clamping head on the sealing bar.
The measurement cables UML-1 and UML-2 are twisted cables used for voltage mea-
surement in conjunction with RESISTRON
®
and CIRUS
®
temperature controllers.
Further information can be found on the measurement cable data sheet.
4.6 Optional system components
4.6.1 Booster
If the continuous current is greater than 5A or the pulsed current is greater than 25A,
use abooster; refer to section How to order. Refer to the application report for more
detailed information.