Functions and settings | 8
VERSION 1 | EN-US CIRUS
®
UPT-6400 Page 55 of 104
When the variable base temperature is specified via an external input, the external
voltage must be activated at least 200ms before AUTOCAL is performed. Otherwise
the base temperature will not achieve the desired value.
If the specified temperature is too high (greater than 40 °C) or if the specified value
fluctuates, an error message appears (error code s115 and116,; refer to section Error
messages [}84]).
The automatic calibration takes approx. 10…15 sec. The heating element is not
heated additionally during this process. During AUTOCAL, the message "Calibration -
please wait" appears on the screen and a timer counts down from 15 to 0. The actual
value output (terminals 17+18) changes to 0…3 °C (corresponds to approx. 0 VDC)
during this time.
Fluctuating
temperature
If the temperature of the heating element fluctuates, the AUTOCAL function is exe-
cuted a maximum of three times. If the function still cannot be executed successfully,
an error message appears; refer to section Error messages [}84].
AUTOCAL function is
disabled
AUTOCAL is disabled if any of the following conditions occur:
• In the first 10sec, if the temperature controller does not report an alarm after be-
ing switched on reset, and the cooling rate is lower than 0.1K/sec. The tempera-
ture controller indicates in the Settings menu, menu number107: "Heating ele-
ment still warm! Please wait..."
• The cooling rate of the heating element is greater than 0.1K/s. The temperature
controller indicates in the Settings menu, menu number107: "Heating element
still warm! Please wait..."
Note: If the AUTOCAL signal is activated and the cooling rate has fallen below
0.1K/s, the temperature controller carries out the AUTOCAL function.
• The START signal is active. The temperature controller indicates in the Settings
menu, menu number107 "AUTOCAL is disabled! (START signal active...)"
• The DETACH signal is active. The temperature controller indicates in the Set-
tings menu, menu number107 "AUTOCAL is disabled! (DETACH signal ac-
tive...)"
• The RESET signal is active. The temperature controller indicates in the Settings
menu, menu number107 "AUTOCAL is disabled! (RESET signal active...)"
• Error codes 101…103, 201…203 or 9xx occur directly after switching on the tem-
perature controller; refer to section Error messages [}84]. The temperature con-
troller indicates in the Settings menu, menu number107: "AUTOCAL blocked!
(ALARM active)."
• if the temperature controller has operated correctly at least once after being
switched on and error codes201 to203 or9xx occur; refer to section Error mes-
sages [}84]. The temperature controller indicates in the Settings menu, menu
number107: "AUTOCAL blocked! (ALARM active)."
8.2.4 Configuring alarm relay
The alarm relay can be configured in the Machine menu, menu number405. The fol-
lowing settings are possible:
Setting Description
Normal Alarm relay contact closes when an alarm occurs.
Inverse Alarm relay contact opens when an alarm occurs.
8.2.5 START signal
There are different ways to activate heating using the START signal, depending on the
state of the timer: