EasyManua.ls Logo

Ropex CIRUS UPT-6400 - Setting Sealing Time; Setting Cooling Mode

Ropex CIRUS UPT-6400
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 | Functions and settings
Page 70 of 104 CIRUS
®
UPT-6400 VERSION 1 | EN-US
Actual
temperature
ST
ART signal
T
t
t
0
0
t
1
t = Setting start delay
1
Illustration25: Start delay
The start delay can be set within the range 0…9.98 sec. The default is a 0sec delay.
Heating begins immediately after the START signal is activated.
8.6.3 Setting sealing time
Enter the sealing time in the Settingsmenu, menu number104.
The following settings are possible:
Setting Description
0...99.98 sec The start delay can be set within the range 0…
99.98 sec. The default is 0.1sec.
External The sealing time is controlled by the START signal
(terminals5+6). Sealing continues for as long as
the START signal is active.
Actual
temperature
ST
ART signal
T
t
t
0
0
t
2
t = Heating phase
2
Illustration26: Setting sealing time
8.6.4 Setting cooling mode
Various processes related to the cooling phase can be specified in the Machine
menu, menu number402 on the temperature controller.
The following settings are possible:
Setting Description
Absolute (default) Cooling ends when the actual temperature of the
heating element has fallen to a specified tempera-
ture value. The cooling temperature can be set in
the Settings menu, menu number105.

Table of Contents