8 | Functions and settings
Page 76 of 104 CIRUS
®
UPT-6400 VERSION 1 | EN-US
OFF
t
ON
ON
OFF
External switch
t
START signal
0
t
t
180
°C
80°C
Actual temperature
Relay K1
95% of 180°C
1 sec.
closed
open
Illustration30: Chronological sequence
Essential settings
These setting for the temperature control timer are essential (The fundamental set-
tings such as temperature range, temperature coefficient, etc. are made before). Make
the settings in the sequence specified here.
Menu number in the configuration
menu
Setting
401 (timer) ON
402 (cooling mode) Absolute
404 (beginning of sealing time) When temperature reached
407 (function of relayK1) Active with external switch or start signal
101 (sealing temperature) 180°C
403 (start delay) 0.0 sec
104 (sealing time) 1.0 sec
105 (cooling temperature) Cooling temperature = 80°C
8.7 Recipes
8.7.1 Recipe control
Recipe control enables quickly changing between various configurations of the tem-
perature controller. All of the menu items relevant to a sealing process are saved in a
recipe. This allows various products that are to be produced to be saved in the tem-
perature controller.
Nine different recipes can be saved in the temperature controller.
Menu items in a recipe
The following menu items are saved in a recipe: