6 Startup
6.1 Note on startup
NOTICE
Malfunctioning due to use of devices from other manufacturers
Devices from other manufacturers can lead to malfunctions in the control loop.
Use only original ROPEX accessories.
Use only system components manufactured by ROPEX or that are approved for
use with ROPEX equipment.
6.2 Initial startup
NOTICE
Property damage due to incorrect settings or sealing temperatures that are too
high
Entering the sealing temperature via the analog input can lead to incorrect settings on
the temperature controller or to sealing temperatures that are too high.
Before beginning the sealing process, use a voltage meter to check the specified
voltage value.
Prerequisite
When the temperature controller is started for the first time and when it is restarted af-
ter changing the heating element, proceed as follows:
The following requirements have to be met:
ü The device is completely assembled; refer to section Device assembly [}19].
ü The device is completely connected; refer to section Installation of device [}21].
ü Line voltage is switched off.
ü Confirmation that equipment is de-energized.
ü Heating element is cold.
1. Verification that no START signal is activated.
2. Switch on line voltage.
A switchon message appears on the screen for approx. 2sec, showing the proper
way to switch on the temperature controller.
Screen content Measure
Standard content Proceed with the next step.
Error codes 104, 105, 106, 111, 112,
113, 211
These error codes indicate errors that
can be remedied in the course of
startup.
Other error codes For error diagnosis, refer to section Error mes-
sages [}84]
Configure the device.
Perform this step only upon initial startup.
The following settings are essential: