8 | Functions and settings
Page 72 of 104 CIRUS
®
UPT-6400 VERSION 1 | EN-US
• Cooling temperature in°C (if "absolute" is selected in menu number402): The
cooling ends if the internal time ends, if the actual temperature of the heating ele-
ment falls below the set temperature. The minimum temperature that can be set is
20°C. The default is 50°C.
The setting range is limited by the maximum value specified in the Heating el-
ement menu, menu number306 or by the temperature range set in the Heating
element menu, menu number 305.
• Cooling temperature in% (if "relative" is selected in menu number402): The cool-
ing phase of the internal time ends when the actual temperature has fallen to the
set proportion of the setpoint temperature. Any settings within the range 20…
100% are possible. The default is 40%.
• Cooling temperature in seconds (if "Time" is selected in menu number402): The
cooling phase ends when the time set here has elapsed. The setting range is 0…
99.98 sec. The default is 1.00sec.
8.6.6 Setting beginning time of sealing
The requirement for starting the set sealing time (Settings menu, menu num-
ber104) can be set in the Machine menu, menu number404.
The following settings are possible:
Setting Description
Begin heating upon start The parameterized sealing time begins immedi-
ately after the set start delay has elapsed (Ma-
chine menu, menu number403). When the start
delay is 0 sec, sealing begins as soon as the
START signal is activated.
When the temperature is reached
(default)
Heatup begins immediately after the set start de-
lay has elapsed (Machine menu, menu num-
ber403). The set sealing time does not begin until
the actual temperature of the heating element has
reached 95% of the setpoint temperature.
The following illustration shows the two possible settings: