Functions and settings | 8
VERSION 1 | EN-US CIRUS
®
UPT-6400 Page 59 of 104
18
17
+
+-
100
Z
°
C
200
3000
ROPEX
Temperature controller
GND
max. 5 mA
Actual value
output
0...10 VDC
0...10 VDC
Temperature
display
Voltage values
• 0 VDC: 0°C
• 10 VDC: 300°C or 500°C (depending on device configuration)
The correlation between the change in the output voltage and the actual temperature
is linear.
Temperature T
Voltage U VDC
Range of 0 - 300 °C
°C
300
270
240
210
180
150
120
90
60
20 °C
1
0.66 V
"ZERO"
2 3 4 5 6 7 8 9 10
Temperature T
Voltage U VDC
Range of 0 - 500 °C
°C
500
450
400
350
300
250
200
150
100
20 °C
1
0.4 V
"ZERO"
2 3 4 5 6 7 8 9 10
Temperature range
Only two temperature ranges – 300°C or 500°C – can be output at this actual value
output. A temperature range of 200°C for the temperature controller set in the Heat-
ing element menu, menu number305 is output at this output within the range of
0…300°C. The temperature range 400°C is output with 0…500°C. A display instru-
ment can be connected to this output to show the temperature of the heating element.