EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-352-1 - Setting Calculation; Point-On-Wave Timer Pickup (Pcapu, Pcbpu, Pccpu)-Scheme 2

Schweitzer Engineering Laboratories SEL-352-1
444 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 20010731 Close Logic 4-13
SEL-352-1, -2 Instruction Manual
on-wave closing. These are available on Interface Board 5. See Section 2: Installation. The
logic and output contact operations occur in 200 ms or less. This output contact assignment is
different from the standard output contact assignments (OUT101 = 86BFT). The point-on-wave
logic directly controls the output contact hardware specified by the close settings CLSA, B, and
C. The standard output assignments also control the output contacts, but only every 1/8 cycle.
CLSA, B, and C control the outputs immediately. The default settings are OUT301, OUT302,
and OUT303.
Setting Calculation
Point-On-Wave Timer Pickup (PCApu, PCBpu, PCCpu)–Scheme 2
Detection of a positive trapped charge causes the logic to close the relay output contact at a
positive peak. For negative trapped charge, the logic closes the output contact at a negative
peak. The PCApu timer provides the delay for the breaker close time and any offset to move the
closing point to another point on the wave.
For example, with a Tclose (nominal closing time of the breaker) time of 33 ms (2 cycles) and a
setting of PCApu = 0, the breaker will close at the appropriate peak 2 cycles after the output
contact closes. However, if the Tclose time is 29 ms (1.75 cycles), the breaker would close 1/4
cycle before the peak.
To set PCApu for breaker and offset times that are not multiples of 1 cycle, subtract the
fractional part from 1 cycle and set PCApu to this number. For example, the 1.75-cycle breaker
requires a PCApu setting of 1 minus the fractional part of 1.75 (0.75), which equals 0.25 (1–0.75
= 0.25). PCApu is set in ms; therefore, PCApu = 4.17 ms for a nominal 60 Hz system.
An offset may be included in the timer as well. For example, a breaker that nominally closes in
38.9 ms but has a tolerance of 0.5 ms for temperature variation, and +1/–2 ms for control
voltage variation, needs an offset to provide the best closing results. The total error band is
+1.5/–2.5 ms. This error band should be centered around the point of closing. It needs to shift
0.5 ms in the positive direction. Set PCApu = [1 – fractional part of (38.9/16.67)] • 16.67 + 0.5 =
11.61 ms.
Figure 4.10: Point-On-Wave Timer Calculation

Table of Contents