G-6 Distributed Network Protocol (DNP) 3.00 Date Code 20010731
SEL-352-1, -2 Instruction Manual
OBJECT TABLE
The following object table lists supported objects, functions, and qualifier code combinations.
Table G.2: SEL-352 Relay DNP Object Table
Object
Request
(supported)
Response
(may generate)
Obj.
*default
Var.
Description
Function
Codes
(decimal)
Qualifier
Codes
(hex)
Function
Codes
(decimal)
Qualifier
Codes
(hex)
1 0 Binary Input–All Variations 1 0,1,6,7,8
1 1 Binary Input 1 0,1,6,7,8 129 0,1,7,8
1 2* Binary Input With Status 1 0,1,6,7,8 129 0,1,7,8
2 0 Binary Input Change–All Variations 1 6,7,8
2 1 Binary Input Change Without Time 1 6,7,8 129 17,28
2 2* Binary Input Change With Time 1 6,7,8 129,130 17,28
2 3 Binary Input Change With Relative Time 1 6,7,8 129 17,28
10 0 Binary Output–All Variations 1 0,1,6,7,8
10 1 Binary Output
10 2* Binary Output Status 1 0,1,6,7,8 129 0,1
12 0 Control Block–All Variations
12 1 Control Relay Output Block 3,4,5,6 17,28 129 echo of
request
12 2 Pattern Control Block
12 3 Pattern Mask
20 0 Binary Counter–All Variations 1 0,1,6,7,8
20 1 32-Bit Binary Counter
20 2 16-Bit Binary Counter
20 3 32-Bit Delta Counter
20 4 16-Bit Delta Counter
20 5 32-Bit Binary Counter Without Flag 1 0,1,6,7,8 129 0,1,7,8
20 6* 16-Bit Binary Counter Without Flag 1 0,1,6,7,8 129 0,1,7,8
20 7 32-Bit Delta Counter Without Flag
20 8 16-Bit Delta Counter Without Flag
21 0 Frozen Counter–All Variations
21 1 32-Bit Frozen Counter
21 2 16-Bit Frozen Counter
21 3 32-Bit Frozen Delta Counter
21 4 16-Bit Frozen Delta Counter
21 5 32-Bit Frozen Counter With Time of Freeze
21 6 16-Bit Frozen Counter With Time of Freeze
21 7 32-Bit Frozen Delta Counter With Time of Freeze
21 8 16-Bit Frozen Delta Counter With Time of Freeze
21 9 32-Bit Frozen Counter Without Flag
21 10 16-Bit Frozen Counter Without Flag
21 11 32-Bit Frozen Delta Counter Without Flag
21 12 16-Bit Frozen Delta Counter Without Flag
22 0 Counter Change Event–All Variations 1 6,7,8
22 1 32-Bit Counter Change Event Without Time 1 6,7,8 129 17,28