Date Code 20010731 Serial Port Communications and Commands 8-37
SEL-352-1, -2 Instruction Manual
=>SHO P<ENTER>
PROTO = SEL
SPEED = 2400 D_BITS = 8 PARITY = N STOP = 1
TIMEOUT= 5 AUTO = N RTS_CTS= N FAST_OP= N
=>
SHO R (Show Report Settings)
Access Level 1
SHOWSET R displays the relay report settings. The report settings include the alias name
assignments, the breaker alarms, a report label, and sequential event record trigger conditions.
The syntax of the SHO R command follows:
SHO R setting<ENTER>
setting specifies the setting name to immediately jump to. The default is the first setting.
Settings cannot be entered or modified with this command. Change settings with the SET R
command from Access Level 2. The following example shows the factory default settings.
Refer to Section 7: Setting the Relay for a list of all settings.
=>SHO R<ENTER>
ALIAS1 =NA
ALIAS2 =NA
ALIAS3 =NA
ALIAS4 =NA
ALIAS5 =NA
ALIAS6 =NA
ALIAS7 =NA
ALIAS8 =NA
ALIAS9 =NA
ALIAS10=NA
ALIAS11=NA
ALIAS12=NA
ALIAS13=NA
ALIAS14=NA
ALIAS15=NA
ALIAS16=NA
ALIAS17=NA
Press RETURN to continue
ALIAS18=NA
ALIAS19=NA
ALIAS20=NA
BALRM =FTRS FCRS 52ACV CWO TWO BDNC BPF CAMT MCC ST SC PTD
LABEL =Example Report Label
SER1 =NA
SER2 =NA
SER3 =NA
=>