4-22 Close Logic Date Code 20010731
SEL-352-1, -2 Instruction Manual
OUTPUT CONTACT
All relay logic must be programmed to an output contact for external indication and control. For
example, the 86BFT bit is the output of the lockout relay control logic. To use this logic,
program an output contact to follow the 86BFT bit (OUT101 = 86BFT).
Note that all outputs will return to their de-energized state (SEL
OGIC control equation = 0) for
approximately 1 second when settings are saved.