Date Code 20010731 Distributed Network Protocol (DNP) 3.00 G-15
SEL-352-1, -2 Instruction Manual
Row SEL-352 Relay Word Bits
Binary
Input
Point
SELOGIC Control Equation SET B Elements
57 L2CR L2CS L2BQ L2BR L2BS L2AQ L2AR L2AS 447–440
58 L3CS L3BQ L3BR L3BS L3AQ L3AR L3AS L2CQ 455–448
59 T2CD T2C T2BD T2B T2AD T2A L3CQ L3CR 463–456
60 L4CR L4CS L4BQ L4BR L4BS L4AQ L4AR L4AS 471–464
61 L5CS L5BQ L5BR L5BS L5AQ L5AR L5AS L4CQ 479–472
62 T3CD T3C T3BD T3B T3AD T3A L5CQ L5CR 487–480
63 L6CR L6CS L6BQ L6BR L6BS L6AQ L6AR L6AS 495–488
64 L7CS L7BQ L7BR L7BS L7AQ L7AR L7AS L6CQ 503–496
65 * * * SBC SBB SBA L7CQ L7CR 511–504
Logic Output Elements
66 UBBF UBPF FOBF FOPF CTF TTF LBF LPF 519–512
67 RTC RTB RTA CCC CCB CCA LODBF LODPF 527–520
68 * * * * * * * FBF 535–528
86BF Trip and Reset Elements
69 M2D M2 L1MQ L1MR L1MS M1D M1 M86T 543–536
70 L3MQ L3MR L3MS M3D M3 L2MQ L2MR L2MS 551–544
71 * MER 86BFT 86RS MDT M4D M4 * 559–552
72 * * * * * CTC CTB CTA 567–560
Contact Output Elements and Display Points
73 !ALARM OUT107 OUT106 OUT105 OUT104 OUT103 OUT102 OUT101 575–568
74 OUT201 OUT202 OUT203 OUT204 OUT205 OUT206 OUT207 OUT208 583–576
75 OUT209 OUT210 OUT211 OUT212 OUT213 OUT214 OUT215 OUT216 591–584
76 OUT301 OUT302 OUT303 OUT304 OUT305 OUT306 OUT307 OUT308 599–592
77 OUT309 OUT310 OUT311 OUT312 OUT313 OUT314 OUT315 OUT316 607–600
78 DP8 DP7 DP6 DP5 DP4 DP3 DP2 DP1 615–608
79 DP16 DP15 DP14 DP13 DP12 DP11 DP10 DP9 623–616
*Reserved for future use.
Relay Summary Event Data
Whenever there is unread relay event summary data (fault data), binary input point 1619 will be
set. In order to load the next available relay event summary, the master should pulse binary
output point 41. This will cause the event summary analogs (points 68–79) to be loaded with
information from the next oldest relay event summary. Since the summary data is stored in a
first-in, first-out manner, loading the next event will cause the data from the previous load to be
discarded. The event summary analogs will retain this information until the next event is loaded.
If no further event summaries are available, attempting to load the next event will cause the
event type analog (point 68) to be set to 0.