D-2 Configuration, Fast Meter, and Fast Operate Commands Date Code 20010731
SEL-352-1, -2 Instruction Manual
MESSAGE DEFINITIONS
A5C0 Relay Definition Block
In response to the A5C0 request, the relay sends the following block:
Data
Description
A5C0 Command
2A Length
02 Support three protocols, SEL, LMD, and DNP
01 Support one Fast Meter message
03 Three status flag commands
A5C1 Fast Meter configuration command
A5D1 Fast Meter command
0002 Self-test warning bit
5354410D0000(STA<CR>) Check status (ASCII characters, <CR>, binary zeros)
0003 Self-test failure bit
5354410D0000(STA<CR>) Check status (ASCII characters, <CR>, binary zeros)
0004 Settings change bit
A5C100000000 Reconfigure Fast Meter configuration (hex)
0100 SEL protocol, Fast Operate
0101 LMD protocol, Fast Operate
0005 DNP protocol
00 Reserved for future use
checksum 1-byte checksum of preceding bytes
A5C1 Fast Meter Configuration Block
In response to the A5C1 request, the relay sends the following block:
Data
Description
A5C1 Fast Meter command
94 (hex) Length
01 One status flag byte
01 Scale factors in Fast Meter configuration message
03 Three scale factors
09 Nine analog input channels
04 Four samples per channel
50 (hex) 80 digital banks
02 Two calculation blocks
0004 Analog channel offset
004C Time stamp offset
0054 Digital offset
564158000000 Analog channel name (VAX)
00 Analog channel type (integer)
01 Scale factor type (float)
008A Scale factor offset (hex)
494100000000 Analog channel name (IA)
00 Analog channel type (integer)