2 Command Summary Date Code 20010731
SEL-352-1, -2 Instruction Manual
ASCII
Command
Command Description
Minimum
Access
Level
Front-
Panel
Equivalent
PAS
PAS n
PAS n pass
Show access level passwords.
Show Access Level n password (n = 1, 2, or B).
Change Access Level n password to pass (pass = up to 6 letters,
numbers, periods, or hyphens).
2
2
2
SET
PUL n k Pulse output contact n (n = output contact element name, i.e.,
OUT201) for k seconds (k = 1 to 30). If k is not specified, 1
second is used. JMP6B must be in place.
B
QUI Quit. Returns to Access Level 0. 0 OTHER
R_S Restore factory default settings. 2
SER d1 d2
SER C
Show rows in the Sequential Events Recorder (SER) from date
d1 to date d2. No date parameters show all records. d2 defaults
to d1 if not specified. Entry of dates is dependent on the Date
Format setting DATE_F (= MDY or YMD).
Clear the sequential events records.
1
2
EVENTS
SET n
SET G
SET P n
SET R
SET T
setting
TERSE
Edit group n (n = 1, 2, or 3) relay settings.
Edit global (inputs, relay configuration) settings.
Edit serial port n (n = 1 to 4) settings. Defaults to the port
issuing the command.
Edit reporting (Aliases, SER, BALARM) settings.
Edit Local Bit and Display Point text settings.
Give a setting name to jump to that setting immediately.
The TERSE option disables the setting verification display.
2
2
2
2
2
SET
SET
SHO n
SHO G
SHO P n
SHO R
SHO T
setting
A
Show group n (n = 1, 2, or 3) relay settings.
Show global (inputs, relay configuration) settings.
Show serial port n (n = 1 to 4) settings. Defaults to the port
issuing the command.
Show reporting (Aliases, SER, BALARM) settings.
Show Local Bit and Display Point text setting.
Give a setting name to jump to that setting immediately.
The A option includes hidden settings in the display.
1
1
1
1
1
SET
SET
STA Display the relay self-test status. 1 STATUS
TAR n k
Display Relay Word row corresponding to n (n = row # or bit
name) k times on the screen.
1
TAR F n k Same as TAR command, but the lower row of front-panel LEDs
are remapped to follow the displayed Relay Word row.
1
TAR R Reset latching targets, display Relay Word Row 0 on the screen
and display Relay Word Row 0 and Row 1 on the target LEDs.
1 TARGET
RESET
X View Relay Word Row without changing default row. 1
TIM
TIM t1
Display relay time (24 hour time).
Set relay time to t1 (t1 = h:m:s, seconds are optional)
1
OTHER
OTHER
TRI Trigger an event report. INT is reported for the event type. 1