D-6 Configuration, Fast Meter, and Fast Operate Commands Date Code 20010731
SEL-352-1, -2 Instruction Manual
2C Operate code, set remote bit RB13
4C Operate code, pulse remote bit RB13
0D Operate code, clear remote bit RB14
2D Operate code, set remote bit RB14
4D Operate code, pulse remote bit RB14
0E Operate code, clear remote bit RB15
2E Operate code, set remote bit RB15
4E Operate code, pulse remote bit RB15
0F Operate code, clear remote bit RB16
2F Operate code, set remote bit RB16
4F Operate code, pulse remote bit RB16
00 Reserved
1-byte Checksum of all preceding bytes
A5E0 Fast Operate Remote Bit Control
Fast Operate Remote Bit Control is suspended during relay setting changes, a setting group
change, power-up, or if the relay is disabled. The external device sends the following message to
perform a remote bit operation:
Data
Description
A5E0 Command
06 Message length (hex)
1-byte Operate code:
00 - 0F clear remote bit RB1 - RB16
20 - 2F set remote bit RB1 - RB16
40 - 4F pulse (1/8 - cycle) remote bit RB1 - RB16
1-byte Operate validation: 4 ¼ Operate code + 1
1-byte Checksum of all preceding bytes
The relay performs the specified remote bit operation if the following conditions are true:
The Operate code is a valid code
The Operate validation = 4 ¼ Operate code + 1
The message checksum is valid
The FAST_OP port setting is set to Y
The relay is enabled
Remote bit set and clear operations are latched by the relay. Remote bit pulse operations assert
the remote bit for one processing interval (1/8 cycle).