Date Code 20010731 Relay Word F-5
SEL-352-1, -2 Instruction Manual
Elements
Alphabetically
Description Relay Word
Row
86BFT
86RS
There is also an 86BFT and 86RS Target LED that may be
viewed with the TAR command, but they cannot be
used in logic.
0
0
87F
87FOA
87FOB
87FOC
Maximum voltage across breaker after Flashover for A-, B-,
or C-phase and a general element indicating any phase
7
3
4
4
87H
87HA
87HB
87HC
Voltage across breaker required to cause pole flashover for
A-, B-, or C-phase and a general element for assertion
of any phase
7
9
9
9
87TH
87THA
87THB
87THC
Voltage across the breaker required to enable the Thermal
model for A-, B-, or C-phase and a general element for
assertion of any phase
7
3
4
4
A A-phase Target LED indicates an A-phase operation
condition. View this bit with the TAR command, but it
cannot be used in logic.
1
AF
AFD
Load current logic timer 62AF Input (AF) and output
(AFD)
33
33
AP
APD
Load current logic timer 62AP input (AP) and output (APD) 33
33
B B-phase target LED indicates a B-phase operation
condition. View this bit with the TAR command, but it
cannot be used in logic.
1
BALRM Breaker Alarm condition, see BALRM setting 54
BCW Breaker Wear Alarm 16
BDNC Breaker Did Not Close alarm 53
BPF Blown Potential Fuse alarm 53
C C-phase target LED indicates a C-phase operation
condition. View this bit with the TAR command, but it
cannot be used in logic.
1
CAMT Current After Motor operated disconnect Trip alarm 53
CCA
CCB
CCC
Controlled Close output for A-, B-, or C-phase 67
67
67
CCT
CCTD
Point-on-wave automatic close input timer input and output 50
50