3-52 Protection Functions Date Code 20080110
SEL-387E Instruction Manual
Time Overcurrent Curve Reference Information
tp = operating time in seconds
tr = electromechanical induction-disk emulation reset time in seconds
(if electromechanical reset setting is made)
TD = time-dial setting
M = applied multiples of pickup current [for operating time (tp), M>1; for reset time (tr), M1]
U.S. Moderately Inverse Curve: U1
=
+=
2
02.0
M1
08.1
TDtr
1M
0104.0
0226.0TDtp
U.S. Inverse Curve: U2
=
+=
2
2
M1
95.5
TDtr
1M
95.5
180.0TDtp
U.S. Very Inverse Curve: U3
=
+=
2
2
M1
88.3
TDtr
1M
88.3
0963.0TDtp
U.S. Extremely Inverse Curve: U4
=
+=
2
2
M1
67.5
TDtr
1M
67.5
0352.0TDtp
U.S. Short-Time Inverse Curve: U5
=
+=
2
02.0
M1
323.0
TDtr
1M
00342.0
00262.0TDtp
I.E.C. Class A Curve (Standard Inverse): C1
=
=
2
02.0
M1
5.13
TDtr
1M
14.0
TDtp
I.E.C. Class B Curve (Very Inverse): C2
=
=
2
M1
3.47
TDtr
1M
5.13
TDtp
I.E.C. Class C Curve (Extremely Inverse): C3
=
=
2
2
M1
0.80
TDtr
1M
0.80
TDtp
I.E.C. Long-Time Inverse Curve: C4
=
=
M1
0.120
TDtr
1M
0.120
TDtp
I.E.C. Short-Time Inverse Curve: C5
=
=
2
04.0
M1
85.4
TDtr
1M
05.0
TDtp

Table of Contents