EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-387E - Data Map

Schweitzer Engineering Laboratories SEL-387E
578 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
G-10 Distributed Network Protocol (DNP3) Date Code 20080110
SEL-387E Instruction Manual
D
ATA
M
AP
The following is the default object map supported by the SEL-387E Relay (see Appendix A:
Firmware and Manual Versions).
Table G.3: SEL-387E-Wye/Delta DNP Data Map
DNP Object Type Index Description
01,02 000–799 Relay Word, where OCA is 0 and TRIP1 is 319.
01,02 800–1599 Relay Word from the SER, encoded same as inputs
000–799 with 800 added.
01,02 1600–1615 Relay front-panel targets, where 1615 is A, 1608 is
50/51, 1607 is EN, and 1600 is 24.
01,02 1616 Relay disabled.
01,02 1617 Relay diagnostic failure.
01,02 1618 Relay diagnostic warning.
01,02 1619 New relay event available.
01,02 1620 Settings change or relay restart.
10,12 00–15 Remote bits RB1–RB16.
10,12 16 Pulse Open breaker 1 command OC.
10,12 17 Pulse Close breaker 1 command CC.
10,12 18 Pulse Open breaker 2 command OC.
10,12 19 Pulse Close breaker 2 command CC.
10,12 20 Pulse Open breaker 3 command OC.
10,12 21 Pulse Close breaker 3 command CC.
10,12 22–29 Remote bit pairs RB1–RB16.
10,12 30 Open/Close pair for breaker 1.
10,12 31 Open/Close pair for breaker 2.
10,12 32 Open/Close pair for breaker 3.
10,12 33 Reset demands.
10,12 34 Reset demand peaks.
10,12 35 Reset breaker monitor.
10,12 36 Reset front-panel targets.
10,12 37 Read next relay event.
10,12 38 Reset energy metering.
20,22 00 Active settings group.