Date Code 20080110 Compressed ASCII Commands E-7
SEL-387E Instruction Manual
The relay responds:
<STX>
"FID","yyyy"<CR>
"FID=SEL-387E-XXXX-V-ZXXXXXX-DXXXXXXXX","yyyy"<CR>
"MONTH_","DAY_","YEAR_","HOUR_","MIN_","SEC_","MSEC_","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"yyyy"<CR>
"FREQ","SAM/CYC_A","SAM/CYC_D","NUM_OF_CYC","EVENT","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,"xxxx","yyyy"<CR>
"IOP1","IRT1","I1F2","I1F5", "IOP2","IRT2","I2F2","I2F5","IOP3","IRT3","I3F2","I3F5",
"TRIG","DIGITAL_ELEMENT_NAMES","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"z","RLY_BITS","yyyy"
<CR> ... (previous line repeated for SAM/CYC_A*NUM_OF_CYC)
"SETTINGS","yyyy"<CR>
"SETTINGS text","yyyy"<CR>
<ETX>
Note: "DIGITAL_ELEMENT_NAMES" consists of the text strings representing the names for
the Relay Word bits from the element store visible to the user, excluding the first 2 front-
panel rows.
where:
xxxx are the data values corresponding to the first line labels.
yyyy is the 4-byte ASCII representation of the hex checksum for the line.
z is ">" to mark where the event was triggered, "*" to mark the maximum current
for the event, with the "*" overriding the ">"
RLY_BITS relay element data, in hex ASCII, corresponding to the
DIGITAL_ELEMENT_NAMES
SETTINGS text refers to the current settings of the relay as described in the event report
section.
CHISTORY C
OMMAND
Display the SEL-387E Relay Compressed ASCII history report by sending:
CHI <Enter>
The relay sends:
<STX>
"FID","yyyy"<CR>
"FID=SEL-387E-XXXX-V-ZXXXXXX-DXXXXXXXX","yyyy"<CR>
"MONTH_","DAY_","YEAR_","HOUR_","MIN_","SEC_","MSEC_","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"yyyy"<CR>
"REC_NUM","MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC","EVENT",
"GROUP", "TARGETS", "yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"xxxx",xxxx,"xxxx", " yyyy"<CR>
... (continue previous line until all events are listed—max 99)
<ETX>