3-36 Protection Functions Date Code 20080110
SEL-387E Instruction Manual
Figure 3.15: 50Pn1 Phase Definite-Time O/C Element, Torque Controlled
50Pn2 – Phase Instantaneous Element
Figure 3.16 shows the logic for the 50P
n
2 element. The 50P
n
2 element logic compares
magnitudes of phase input currents IAW
n
, IBW
n
, and ICW
n
to pickup setting 50P
n
2P. If one or
more current magnitudes exceed the pickup level, a logic 1 asserts at one input to the AND gate.
The torque-control SEL
OGIC
control equation 50P
n
2TC determines the other AND input. If
50P
n
2TC is true, Relay Word bit 50P
n
2 asserts.
Figure 3.16: 50Pn2 Phase Instantaneous O/C Element, Torque Controlled
50Pn3 and 50Pn4 – Phase Instantaneous Element
Figure 3.17 shows the logic for the two nontorque-controlled phase instantaneous elements. The
two elements find application primarily in level detection or phase identification. The logic
compares magnitudes of phase input currents IAW
n
, IBW
n
, and ICW
n
to pickup setting
50P
n
3P(4P). Any phase current exceeding the pickup level will assert the appropriate phase-
specific Relay Word bit, 50A
n
3(4), 50B
n
3(4), or 50C
n
3(4). These bits enter an OR gate to assert
Relay Word bit 50P
n
3(4), indicating “any phase” pickup.