EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-387E - Through-Fault Event Monitor Settings

Schweitzer Engineering Laboratories SEL-387E
578 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 20080110 Metering and Monitoring 5-15
SEL-387E Instruction Manual
mechanical stress and the winding insulation to thermal stress. The more feeders on a
distribution bus, the more the transformer bank is exposed to these through faults.
SEL-387
Through-Fault Current
Figure 5.6: Distribution Feeder Faults Expose Transformer Bank to Through Faults
Monitor and document this through-fault activity with the through-fault event monitor in the
SEL-387E Relay. The through-fault event monitor captures maximum current levels, duration,
and date/time for each transformer through fault. The monitor also performs a simple I
2
t
calculation (analogous to the energy expended during the through fault) and cumulatively stores
calculation results for each monitored phase.
Through-Fault Event Monitor Settings
Activate and adjust the through-fault event monitor with the settings in Table 5.2.
Table 5.2: Through-Fault Event Monitor Settings
Setting Definition Range
ETHRU Enable Through-Fault Event Winding N, 1, 2, 3
THRU Through-Fault Event Trigger
(SEL
OGIC control equation
Relay Word bits (Table 4.8)
ISQT Through-Fault I
2
t Alarm Threshold OFF, 0–4294967 (kA)
2
seconds
Setting ETHRU = N turns off the through-fault event monitor. Any other setting selection for
ETHRU designates the winding to monitor for through-fault events. For example, ETHRU = 2
designates Winding 2 as the winding to monitor for through-fault events. Specifically,
Winding 2 current inputs IAW2, IBW2, and ICW2 (A-phase, B-phase, and C-phase,
respectively) are monitored for maximum currents for through-fault events. Changing setting
ETHRU resets/clears through-fault event information (see
TFE C
and
TFE R
command
discussions that follow).
Setting THRU triggers the through-fault event—the through-fault event monitor starts acquiring
maximum current and duration information, along with a date/time tag. Typically, the THRU
setting is set with an overcurrent element. For example, set THRU to trigger a through-fault
event on the pickup of a phase instantaneous overcurrent element on Winding 2:

Table of Contents

Related product manuals