Date Code 20080110 Communications 7-21
SEL-387E Instruction Manual
either mm/dd/yy or yy/mm/dd depending on the SET G date format setting DATE_F. The
following example views the current date, verifies the DATE_F setting, and changes the date.
Note that single-digit numbers may be entered without leading zeros, as in the 9 in 11/9/96.
=>>DAT <Enter>
11/11/96
=>>SHO G DATE_F <Enter>
RELAY SETTINGS
DATE_F = MDY FP_TO = 5 TGR = 5
=>>DAT 11/9/96 <Enter>
11/09/96
=>>
Note: After setting the date, allow at least 60 seconds before powering down the relay or the
new setting may be lost.
EVE (Event Reports)
Access Levels 1, B, 2
Use the EVENT command to view event reports. See Section 9: Analyzing Events for further
details on retrieving event reports.
GRO and GRO n (Setting Group)
Access Levels 1, B, 2
The GRO command, at Access Level 1, displays the setting group variable for the currently
active setting group. Changing the variable is not permitted. The GRO n command, at Levels B
and 2, designates what the setting group variable is to be (n = 1 to 6), thereby asking the relay to
change to the setting group so designated. The relay will only make the change if the setting
group selection SEL
OGIC
control equations (SS1 through SS6) are not assigned or are not
asserted. The following example verifies the existing group variable, changes it, and then waits
for the automatic message when the setting group changes. The variable must be changed for a
certain number of seconds as specified by the TGR setting (under SET G) before the new
settings are enabled.
=>>GRO <Enter>
Active Group = N
=>>GRO 2 <Enter>
Change to Group 2
Are you sure (Y/N) ? Y <Enter>
=>>