D-4 Configuration,
Fast Meter,
and
Fast Operate
Commands Date Code 20080110
SEL-387E Instruction Manual
564443000000 (VDC)
00
01
00DA
1-byte Connection byte—Based on PHROT and W1CT settings (Calculation
block #1)
03 Current calculation only
FFFF No skew adjustment
FFFF No RS offset
FFFF No XS offset
00 IAW1
01 IBW1
02 ICW1
FF NA
FF NA
FF NA
1-byte Connection byte—Based on PHROT and W2CT settings (Calculation
block #2)
03 Current calculation only
FFFF No skew adjustment
FFFF No RS offset
FFFF No XS offset
03 IAW2
04 IBW2
05 ICW2
FF NA
FF NA
FF NA
1-byte Connection byte—Based on PHROT and W3CT settings (Calculation
block #3)
03 Current calculation only
FFFF No skew adjustment
FFFF No RS offset
FFFF No XS offset
06 IAW3
07 IBW3
08 ICW3
FF NA
FF NA
FF NA
1-byte Connection byte—Based on PHROT and DELTA_Y settings
(Calculation block #4)
00 For VIWDG=1 or 2 or 3
02 For VIWDG=12
FFFF No skew adjustment
FFFF No RS offset
FFFF No XS offset
xx 00 if VIWDG=1; 03 if VIWDG=2; 06 if VIWDG=3; FF if VIWDG=12
xx 01 if VIWDG=1; 04 if VIWDG=2; 07 if VIWDG=3; FF if VIWDG=12