188 FLOWSIC100 Flare · Operating Instructions · 8013344/11L2/V 2-5/2018-10 · © SICK Engineering GmbH
Start-up and Parameter Settings
Subject to change without notice
Figure 124 "Parameter / Data archives" directory
Field Parameter Remark
Gas time Hours, minutes
Defines the daily start-time for writing the archives
in order to synchronize the record for multiple
devices
Interval selection Hourly
600 entries are made, max. number of entries is set
by the device
Daily
30 entries are made, max. number of entries is set
by the device
Monthly
12 entries are made, max. number of entries is set
by the device
Free defined Free number of entries (max. 700) and interval
Write mode Overwriting, stopping
„Overwriting mode”:- all stored data will be
overwritten if maximum number of entries is
reached; „Stopping mode”: data recording is
stopped is maximum number of entries is reached
Measuring point
Measuring point 1,
Measuring point 2,
Measuring point 3
Select measure point to make the settings for the
data archive

Table of Contents

Other manuals for SICK FLOWSIC100 Flare

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK FLOWSIC100 Flare and is the answer not in the manual?

SICK FLOWSIC100 Flare Specifications

General IconGeneral
BrandSICK
ModelFLOWSIC100 Flare
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals