48 FLOWSIC100 Flare · Operating Instructions · 8013344/11L2/V 2-5/2018-10 · © SICK Engineering GmbH
Product Description
Subject to change without notice
2.2.1.3 FLSE100-EX and FLSE100-EXRE sender/receiver units
Transducers: medium dimensions
Process connection: prepared for mounting on counter flange 2" CL150 RF acc. to ASME
B16.5 or counter flange DN50 PN16 form B1 acc. to EN 1092-1
I) FLSE100-EX and FLSE100-EXRE sender/receiver units according to ATEX for use in
zone 2 only
Explosion protection: ATEX II 3 G Ex nA IIC T4 Gc
Applied standards: EN 60079-0, EN 60079-15
Fig. 17 FLSE100-EX and FLSE100-EXRE sender/receiver units
FLSE100-EX sender/receiver unit, non-retractable version
2
1 3
Permissible gas pressure/temperature range:
→
pg. 41, Fig. 7
FLSE100-EXRE sender/receiver unit, retractable version (guide rods not shown)
Permissible gas pressure/temperature range:
→
pg. 42, Fig. 9
1 Connection for optional venting
2 Retraction flange
3 Centering
Modules/parts not named:
→
pg. 31, Fig. 5