SIEMENS Energy & Automation 10-9
SIMOREG DC Master Base Drive Panel Operating Instructions
PNU
Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
r022
(G160)
Display of torque setpoint before torque limitation
Steps: 1
=
0.1% of rated motor torque (=rated motor armature current
(P100) * magnetic flux at rated motor field current (P102))
-400.0 to 400.0
[%]
0.1% (see column on
left)
Ind: None
Type: I2
P052 = 3
r023
(G152)
Display of speed controller setpoint/actual value deviation
-200.00 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r024
(G145)
Display of actual speed value from pulse encoder
-200.00 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r025
(G151)
Display of actual speed controller value
-200.0 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r026
(G152)
Display of speed controller setpoint
-200.0 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r027
(G136)
Display of ramp-function generator output
-200.00 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r028
(G136)
Display of ramp-function generator input
-200.00 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r029
(G135)
Display of main setpoint before limitation
-200.00 to 199.99
[%]
0.01%
Ind: None
Type: I2
P052 = 3
r034
(G166)
Display of firing angle (field)
0.00 to 180.00
[degrees]
0.01degrees
Ind: None
Type: O2
P052 = 3
r035
(G166)
Display of field current controller actual value
0.0 to 199.9
[% of P102]
0.1% of P102
Ind: None
Type: O2
P052 = 3
r036
(G166)
Display of field current controller setpoint
0.0 to 199.9
[% of P102]
0.1% of P102
Ind: None
Type: O2
P052 = 3
r037
(G165)
Display of actual EMF value
-1500.0 to 1500.0
[V]
0.1V
Ind: None
Type: I2
P052 = 3
r038 Display of actual armature voltage value
-1500.0 to 1500.0
[V]
0.1V
Ind: None
Type: I2
P052 = 3
r039
(G165)
Display of EMF setpoint
This parameter displays the EMF setpoint which is applied as the control
quantity in the field-weakening range.
This value is calculated from:
Umotor
rated
Imotor
rated
*
RA (= P101 – P100
*
P110)
0.0 to 1500.0
[V]
0.1V
Ind: None
Type: O2
P052 = 3