The following table lists the actions we recommend you take to help secure your device in a
protected environment, organized by life-cycle stage:
Recommended action Defense-in-depth role
Plan
Review cybersecurity
awareness
Resources to increase your cybersecurity knowledge and
awareness.
Review the system
defense in depth
assumptions
Understand the security measures expected to be provided by the
external environment in which the device is to be used.
Review the device security
capabilities
Understand how the device's security capabilities can be used in a
protected environment.
Review the "Security risks
and mitigation strategies"
on page 31
Known security risks and the mitigation strategies to help minimize
the risks.
Review the Security risks
and mitigation strategies
Known security risks and the mitigation strategies to help minimize
the risks.
Configure
Change the default
password *
Help reduce unauthorized access. Default account settings are
oftenthe source of unauthorized access by malicious users.
Disable meter
configuration methods *
Limiting configuration options and providing read-only access
reduces the attack surface of the meter.
Disable webpages and
time sync sources *
Disable webpages to deny a web browser to access the meter
data. If your meter can be accessed by a web browser outside
your protected network, a malicious user could intercept
communications.
Disable the ability to modify the meter’s time source to help protect
against disguised communication from an unknown source as
being trusted and possibly invalidating timestamps.
Define lockouts and event
timeouts *
Lock accounts after a predefined number of unsuccessful login
attempts. Lockouts help reduce brute-force password attacks from
succeeding.
Limit user access*
Limit user access to the minimum, least privilege level of access
needed to perform their job functions.
Revoke user privileges when no longer needed due to role
change, transfer, or termination.
Edit meter access event
logging *
Edit the default meter access event priorities that are logged to the
event log to meet your reporting requirements.
9810 series - User manual Cybersecurity
7EN05-0390-08 24

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 9810 Series and is the answer not in the manual?

Siemens 9810 Series Specifications

General IconGeneral
BrandSiemens
Model9810 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals