Table of the System’s Programming Code
s
A31003-K1250-S100-12-7619
HiPath 1100, Service Manual
7-1
For internal distribution only Configuring the System Specifically for the Client
7 Configuring the System Specifically for the Client
Procedure Summary
7.1 Table of the System’s Programming Codes
The Numbering Plan is configured based on the modules detected by the system.
For the HiPath 1120:
Motherboard
S0 Module
Analog Modules
For the HiPath 1130/1150:
TME1 Module 1
Motherboard
S0 Module
Analog Modules
For the HiPath 1190:
Analog Modules
TME1 Module 1
S0 Module
Table 7-1 Configuration procedure summary
Step System Telephone/Standard MF Telephone HiPath 1100 Manager
1. System programming can only be executed using the sys-
tem’s first extension slot (analog extension (MF) or system
telephone).
Connect the PC to the sys-
tem.
2. Programming Mode: *95 + PASSWORD (default: 31994). Configure CommServer.
3. Valid parameter or slot: beep (Brazil). Start the program.
4. When an incorrect setting is entered: 3 beeps (Brazil). System data are automati-
cally imported.
5. When completed: 1 beep (Brazil). Start programming.
6. End programming: press “#” key or replace handset. Export the new configura-
tion settings.