Special measures to prevent cross-circuits and short-circuits
The routing of cables over longer distances, e.g. between remote control cabinets, increases the
risk of damaging cables. Damaged cables raise the risk of an undetected cross-circuit with power-
conducting cables laid in parallel. A cross-circuit can cause interruption to the transfer of safety-
related signals.
To avoid cross circuit faults and short-circuits, you must protect the cables between a sensor
and the converter; this can be done by routing the cables separately or in a steel pipe/duct
On and o󹪜 test
The converter 󹪝lters signal changes using on and o󹪜 tests at the failsafe digital input using an
adjustable software 󹪝lter.
Installing
4.10Connecting the interfaces for the converter control
SINAMICS G120C Converters
102 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)
Output Voltage0 V to Supply Voltage