8.18.5 Speed limitation
The maximum speed limits the speed setpoint range for both directions of rotation.
0D[LPXPVSHHG
0LQ
0D[


[
\
[
\
W
\\[[
S
S
The converter generates a message (fault or alarm) when the maximum speed is exceeded.
If you must limit the speed depending on the direction of rotation, then you can de󹪝ne speed
limits for each direction.
Parameters
Table 8-52 Parameters for the speed limitation
Number Name Factory setting
p1082[D] Maximum speed 1500rpm
p1083[D] CO: Speed limit in positive direction of rotation 210000rpm
p1085[C] CI: Speed limit in positive direction of rotation 1083
p1086[D] CO: Speed limit in negative direction of rotation -210000rpm
p1088[C] CI: Speed limit in negative direction of rotation 1086
Advanced commissioning
8.18Setpoint processing
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 285