4.2.3 Electromechanical components
Surge voltage protection circuit
Connect surge voltage protection circuits to the following components:
Coils of contactors
Relays
Solenoid valves
Motor holding brakes
Connect the surge voltage protection circuit directly at the coil.
Use RC elements or varistors for AC-operated coils and freewheeling diodes or varistors for
DC-operated coils.
Installing
4.2EMC-compliant setup of the machine or plant
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 45