In the scope of such spare parts-compatible ongoing development, plug connector or
connection positions are sometimes slightly modi󹪝ed. This does not cause any problems
when the components are properly used. Please take this fact into consideration in special
installation situations (e.g. allow su󹪟cient reserve regarding the cable length).
10.1 Replacing the converter hardware
Overview
You may only replace a converter with a di󹪜erent converter under certain preconditions.
Requirement
The following preconditions apply for making a replacement:
The new converter has the same or more recent 󹪝rmware version than that of the converter
being replaced.
The two converters must also satisfy one of the following conditions:
The new and replaced converters have the same power rating.
The new converter has a di󹪜erent power rating than the converter it replaced, but still has
the same frame size.
In this case, the rated power of the converter and the rated motor power must not di󹪜er
too much.
The following values are permissible for the quotients (rated motor power)/(rated
converter power): 0.25 … 1.5
Description
WARNING
Unexpected machine motion caused by incorrect converter type
Replacing converters of di󹪜erent types can result in incomplete or incorrect/inappropriate
converter settings. As a consequence, machines can unexpectedly move, e.g. speed
oscillation, overspeed or incorrect direction of rotation. Unexpected machine motion can result
in death, injury and/or material damage.
In all cases not permitted according to the above precondition, you must recommission the
drive after replacing the converter.
Corrective maintenance
10.1Replacing the converter hardware
SINAMICS G120C Converters
380 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)
Output Voltage0 V to Supply Voltage

Related product manuals