7.2.2 Activating and deactivating know-how protection
Requirements
The converter has now been commissioned.
You have generated the exception list for know-how protection.
To guarantee know-how protection, you must ensure that the project does not remain at the
end user as a 󹪝le.
Function description
Activating know-how protection
1. Enter a password of your choice in p7767.
Each index of p7767 corresponds with a character in the ASCII format.
2. Complete entry of the password with p7767[29]=0.
3. Enter the same password in p7768 as that for p7767.
4. Complete entry of the password with p7768[29]=0.
The know-how protection for the converter is activated.
Deactivating know-how protection
1. Enter the password for the know-how protection in p7766.
Each index of p7766 corresponds with a character in the ASCII format.
2. Complete entry of the password with p7766[29]=0.
The know-how protection for the converter is deactivated.
Parameter
Parameter Description Factory setting
r7758[0...19] KHP Control Unit serial number ---
p7759[0...19] KHP Control Unit reference serial number ---
r7760 Write protection/know-how protection status ---
p7765 KHP con󹪝guration 0000 bin
p7766[0...29] KHP password, input ---
p7767[0...29] KHP password, new ---
p7768[0...29] KHP password, con󹪝rmation ---
p7769[0...20] KHP memory card reference serial number ---
r7843[0...20] Memory card serial number ---
Protecting the converter settings
7.2Know-how protection
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 181

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)
Output Voltage0 V to Supply Voltage

Related product manuals