Rated motor speed
Motor cooling:
: Natural cooling
: Forced-air cooling
: Liquid cooling
: Without fan
Select the appropriate application:
: In all applications that do not 󹪝t the other setting options.
: Applications involving pumps and fans
: Applications with short ramp-up and ramp-down times.
: Applications involving pumps and fans with optimized e󹪟ciency. The setting
only makes sense for steady-state operation with slow speed changes. We recommend
setting if load surges during operation cannot be ruled out.
Select the control mode:
: U/f control with linear characteristic
: Flux current control (FCC)
: U/f control with square-law characteristic
: Sensorless vector control
Commissioning
5.4Quick commissioning using the BOP-2 operator panel
SINAMICS G120C Converters
134 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)
Output Voltage0 V to Supply Voltage